Digital I/O and Relay Output

Counter/Frequency Command Set


7-14 ADAM 4000 Series User’s Manual

$AA2

Name

Configuration Status command

Description

Returns the configuration parameters of the digital I/O
module.

Syntax

$AA2(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

2

is Configuration Status command.

(cr)

is the terminating character, carriage return (0Dh).

This command requests the return of the configuration data
from the digital I/O module at address AA.

Response

!AATTCCFF(cr)

if the command is valid.

?AA(cr)

if an invalid command has been issued.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

?

is a

delimiter character which indicates an invalid

command.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

TT

represents the type of code, which is always 40.

CC

represents the baud rate codes.

(Refer to Table 7-2 on next page).

The hexadecimal number

FF

which is converted to a 8-bit

parameter represents the checksum and protocol status .

Bits 3 through 5 and bit 0, 1, 7 are not used, so they are
set to 0. (Refer to Figure 7-2 on next page)

Bit 6 is the selection of checksum and bit 2 is the selection
of protocol (0: advantech, 1: modbus).

(Modbus protocol is supported by ADAM-4051, 4055,
4056S, 4056SO, 4068 only)

(cr)

is the terminating character, carriage return (ODh).

4050, 4051, 4052, 4053, 4055,

4056S, 4056SO, 4060, 4068, 4069