I/o modules, C, mv, v or ma), Adam-4018 – Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 59

Advertising
background image

I/O Modules


3-32 ADAM 4000 Series User’s Manual

ADAM-4018

8-channel Analog Input Module

ADAM-4018

CODE

INPUT RANGE

00

01

02

03

04

DATA

ACQUISITION

MODULE

V

in 0+

V

in 0-

V

in 1+

V

in 5+

V

in 5-

V

in 6+

IN

IT*

(Y) D

A

TA+

(G

) D

A

TA-

(R

) +

V

s

(B) G

N

D

V

in 1-

V

in 4+

V

in 4-

AG

N

D

INPUT:

Thermocouple

mV, V, mA

OUPUT:

RS-485

05

?5 mV

?0 mV

?00 mV

?00 mV

? V

?.5 V

V

in 7+

V

in 3-

V

in 3+

V

in 2-

V

in 2+

?0 mA

T/C J

T/C K

T/C T

T/C E

T/C R

T/C S

T/C B

06

DE

DF

10

11

12

13

14

Figure 3-27 ADAM-4018 8-channel Thermocouple Input Module


Channels:
- Six differential, two single-ended

Accepts:
- J, K, T, E, R, S and B thermocouples
- Millivolt inputs: ±15 mV, ±50 mV, ±100 mV and ±500 mV
- Volt inputs: ±1 V and ±2.5 V
- Current input: ±20 mA (requires a 125 resistor)

The module forwards the data to the host computer in engineering units
(

o

C, mV, V or mA)


Advertising