Advantech Data Acquisition Modules ADAM 4000 User Manual

Page 277

Advertising
background image

Digital I/O and Relay Output

Counter/Frequency Command Set


7-42 ADAM 4000 Series User’s Manual

$AAA

Name

Read Gate Mode command

Description

Request the specified counter/frequency module to return
its gate status.

Syntax

$AAA(cr)

$

is a delimiter character.

AA

(range 00-FF) represents the 2-character hexadecimal

address that you will access to.

A

is the Read Gate Mode command.

(cr)

is the terminating character, carriage return (0Dh).

Response

!AAG(cr)

if the command is valid.

There is no response if the module detects a syntax or
communication error, or even if the specified address does
not exist.

!

is a delimiter character which indicates a valid command.

AA

(range 00-FF) represents the 2-character hexadecimal

address of the module.

G

determines the gate mode.

G = 0 the gate is low
G = 1 the gate is high
G = 2 the gate is disabled.

(cr)

is the terminating character, carriage return (0Dh).

Example command:

$01A(cr)

response: !011(cr)

The command requests the counter/frequency module to
return its gate status. The module at address 01 replies with
gate setting high.

4080, 4080D