2.0

Menu INPUTS

2.1 Measure Menu

This menu appears when choosing closed loop, inertia correction,motor command or speed
follower. It allows calibration for any type of measurement, from a few mV to 10V.

Measure calibration

% full scale: Type in the percentage of full scale corresponding to the upper point used

during calibration (this percentage must be more than 20%).

Valid high level: Type in the value for the upper point.
Valid low level: Type in the value for the lower point.

Procedure:

Fill the 3 parameters and then click on the memory used. Then physically simulate the upper
point and click "valid high level," wait 5 seconds (yellow button), physically simulate the lower
point and click "valid low level," wait 5 seconds (yellow button); calibration is complete.