Run

(J6 pins 3, 5)
Digital Input 3

When the RUN input (J6, pin 5) is momentarily shorted
to common, the CX–1010 enters the RUN state. As a
momentary input, RUN is internally latched and does
not need to be maintained closed by an operator
device.

NOTE: Close the R–Stop, H-Stop and F–Stop inputs

prior to entering the Run state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX–1010 will not enter run.

Jog Forward

(J6 pins 6, 8)
Digital Input 4

JOG FORWARD is a maintained input. When it is
closed, it sends a forward speed command signal to the
drive at the selected Jog Setpoint . As a maintained
input, JOG FORWARD is only active when the operator
device is closed.

NOTE: Close the R–Stop, H-Stop and F–Stop inputs

prior to entering the Jog state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX–1010 will not enter Jog.

Jog Reverse

(J6 pins 7, 8)
Digital Input 5

JOG REVERSE is a maintained input. When it is
closed, it sends a reverse speed command signal to the
drive at the selected Jog Setpoint . As a maintained
input, JOG REVERSE is only active when the operator
device is closed.

NOTE: Close the R–Stop, H-Stop and F–Stop inputs

prior to entering the Jog state. If you are only
using one of the Stop inputs, wire short the
other Stop inputs to the common or the
CX–1010 will not enter Jog.

Figure 16 Run

RUN

3

5

J6

COM

DI_3

Figure 17 Jog Forward

JOG FORWARD

6

8

J6

DI_4

COM

Figure 18 Jog Reverse

JOG REVERSE

7

8

J6

DI_5

COM