Inputs – CONTREX CX-1010 User Manual

Page 39

Advertising
background image

Page 37

INPUTS

NOTE: Refer to pages 9 and 35 before you begin wiring.

Figure 36 Analog Input 2: Voltage

Input

Figure 35 Analog Input 1: Voltage Input

5

6

7

8

JA

±

12V Input

Common

+

+

2

3

4

8

JA

±

12V Input

Common

+

+

Analog Input 1:
Voltage Input Wiring

(JA, Pins 2, 4, 8)

The Analog Input 1 can be used with either

±

12 VDC or

0-20 mA inputs. Figure 35 displays the

±

12 VDC option.

For the differential inputs:

Connect JA pin 2 to the positive differential signal

source.

Connect JA pin 4 to the negative differential signal

source.

Connect JA pin 8 to the common of the differential

signal source.

For the non-differential inputs:

Connect JA pin 2 to the signal voltage source.
Connect JA pin 4 and JA pin 8 to the common of the

signal source.

Analog Input 2:
Voltage Input Wiring

(JA, Pins 5, 7, 8)

The Analog Input 2 can be used with either

±

12 VDC or

0-20 mA inputs. Figure 36 displays the

±

12 VDC option.

For the differential inputs:

Connect JA pin 5 to the positive differential signal

source.

Connect JA pin 7 to the negative differential signal

source.

Connect JA pin 8 to the common of the differential

signal source.

For the non-differential inputs:

Connect JA pin 5 to the signal voltage source.
Connect JA pin 7 and JA pin 8 to the common of the

signal source

Advertising