CONTREX CX-1010 User Manual

Page 50

Advertising
background image

Page 48

Jog Forward has the fifth highest operating priority. Use Jog Fwd to “Jog” the drive Forward at the rate
indicated in Jog SP (CP-215). The acceleration and deceleration ramps are dictated by Acl Tm Jog (CP-216),
Dcl Tm Jog (CP-218) and Jog SP (CP-215). After the Jog FWD input is deactivated and the ramped
reference has reached “0”, the CX-1010 automatically reverts to the R-Stop operating state.

To activate Jog Forward:

Activate Low (closed to common), Level Sensitive, Not-Latched
Use momentary contact - does not need to be maintained to remain active

RUN

JOG FWD

COMMON

F-STOP

R-STOP

H-STOP

COMMON

JOG FWD

RUN

Close Momentarily

5

6

8

1

2

4

3

J6

R-STOP

H-STOP

F-STOP

Figure 47 Jog Forward Input