MCN System Manual

Hardware Installation

CTI Products, Inc.

68-10833-120

30

power supply is encountered.

CA-80027-100

IN

OUT

NETWORK

PWR

ACT

ERR

DC IN

OPTION A

RESET

SVC

1 2 3 4 5 6 7 8

ON

IN

OUT

NETWORK

PWR

ACT

ERR

DC IN

OPTION A

RESET

SVC

1 2 3 4 5 6 7 8

ON

TO NETWORK IN
OF NEXT MCN MODULE

TO DC POWER SUPPLY

PRODUCTS, INC.

PRODUCTS, INC.

Figure 13 - DC Power Chaining

In the example shown in Figure 14, two power supplies are required, even though
there are only four modules in the system. The second supply is required because
the network cable between the third and fourth modules is greater than the 100
foot cable length maximum for power distribution.

CA-80028-100

IN

OUT

DC IN

IN

OUT

DC IN

IN

OUT

DC IN

IN

OUT

DC IN

>100'

T

T

DC POWER

SUPPLY

DC POWER

SUPPLY

Figure 14 - Power Distribution Example