CONDENSER INLET AIR PLENUM

DCP, Condenser Plenums are used to duct condenser air to the unit. The plenum easily attaches with one
screw (supplied) to the back of the unit. The plenum transitions the condenser inlet air opening to 12 inch
round on the PAC10,12,18, 24 and 36. The PAC60 uses 2-12 inch round.

25 equivalent feet (.25 E.S.P.) of 12 inch round duct can be applied to the PAC10 and 12. 50 equivalent feet
(.25 E.S.P.) of 12 inch round duct can be applied to the PAC18, 24 and 36. 100 equivalent feet (.50 E.S.P.)
of 2-12 inch round ducts can be applied to the PAC60.

To calculate “equivalent feet”, add the length of the condenser intake duct run and the length of the
condenser air discharge duct run...allowing for elbows ( adding 6 equivalent feet per 90° (elbow). This is
total equivalent feet. At any rate, do not exceed the rated E.S.P.

Condenser air plenums can substantially reduce air noise and increase the number of options for solving
difficult cooling problems.

AirBoss has a dedicated blower for the condenser section and a dedicated blower for the evaporator section.
So, the “equivalent feet” may be applied to either or both sections at the same time.

Model

Evaporator

Plenum

Round

Duct

Size

PAC

10

PAC

12

PAC

18

PAC

24

PAC

36

PAC

60

DCP-1

Size/Fits

12 inch

Yes

Yes

No

No

No

No

DCP-2

Size/Fits

12 inch

No

No

Yes

Yes

No

No

DCP-3

Size/Fits

12 inch

No

No

No

No

Yes

No

DCP-4

Size/Fits

2-12 Inch

No

No

No

No

No

Yes

Maximum Approx

Equivalent Feet

(ESP)

-

25

(.20)

25

(.20)

50

(.25)

50

(.25)

50

(.25)

100

(.50)

10

airbossmanpg10

PAC1811 with DCP-2 installed

DCP-2

DCP-4