EVAPORATOR INLET AIR PLENUM

DEP, Evaporator Plenums are used to allow a return air duct to be attached to the unit. The
plenum easily attaches with mounting screws in place of the evaporator grille. The plenum
transitions the return air opening to 10 inch round on the PAC10 & 12, and to a 12 inch round on
the PAC18 and 24. 16 inch duct is used on the PAC36 & 60.

25 equivalent feet of 10 inch round duct can be applied to the PAC10 and 12. 50 equivalent feet
of 12 inch round duct can be applied to the PAC18 and 24. 50 equivalent feet of 16 inch round
duct can be applied to the PAC36. 100 equivalent feet of 16 inch duct can be applied to the
PAC60. This air handling capacity is also found on the OceanAire Polaris water-cooled units.

To calculate “equivalent feet”, add the length of the supply duct run and the length of the return
duct run...allowing for elbows( adding 6 equivalent feet per 90° elbow). This is total equivalent
feet.

Evaporator plenums can substantially reduce air noise and increase the number of options for
solving difficult cooling problems.

AirBoss has a dedicated blower for the evaporator section and a dedicated blower for the
condensing section. So, the “equivalent feet” may be applied to either or both sections at the same
time.

Model

Evaporator

Plenum

Round

Duct

Size

Fits

PAC

10

Fits

PAC

12

Fits

PAC

18

Fits

PAC

24

Fits

PAC

36

Fits

PAC

60

DEP-10

Size/Fits

10 inch Yes

Yes

No

No

No

No

DEP-12

Size/Fits

12 inch

No

No

Yes

Yes

No

No

DEP-16

Size/Fits

16 Inch

No

No

No

No

Yes

Yes

Maximum Approx

Equivalent Feet

(ESP)

25


(.15)

25


(.15)

50


(.25)

50


(.25)

50


(.25)

100


(.50)