IB-23C650

INSTALLATION

PROCESS INPUT SIGNAL CONNECTIONS

Process input connections are shown as follows:

Thermocouple Inputs - see Figure 3

RTD Inputs - see Figure 4

mA Inputs from 2-Wire Transmitters - see Figure 5

mA Inputs from Non 2-Wire Transmitters - see Figure 6

Volt Inputs - see Figure 7

mV Inputs - see Figure 8

Digital Inputs - see Figure 9

Motorized Valve Inputs - see Figure 10

Slidewire Inputs - see Figure 10

NOTE:

Input 2 is available when an option card is installed. Input 2 is an
isolated universal analog input which accepts mV dc, mA dc (2-wire
& non 2-wire), RTD, Thermocouple, and slidewire inputs. Input 2
connections are made as shown in Figures 3 through 10, using the
terminals identified as I/O 2

: General process input signal specifications are:

Open Input Fault Detection: Recover option is user configurable

Input Isolation:

Galvanic isolation using transformers and optical
isolators. The process input circuit is isolated; however, if
a field input is completely floating, it may pick up
electrical noise. Field inputs should be grounded in the
field or at the instrument.

Input Resistance: 10M ohms minimum

Input Common Mode Rating: 45V dc

Common Mode Rejection: 120 dB @ 50/60 Hz

Normal Mode Noise Filter: 20 dB minimum @ 60 Hz

Maximum Normal Mode Voltage: 30V dc (except current input)

Display Accuracy: Input accuracy±one least significant display digit