IB-23C650

SETUP

Table 4. Milliamp Output Setup Menu

Middle

Display

Bottom

Display

Entry Description

UP OUTPT

xx.x

–8.0 to 110.0. Limited by output high and low
limits above.
If heat/cool is used, output value (OV) can be
determined from heat output (HO) or cool
output (CO) and crossover value (CV):

OV (Heat) = CV + {[(100CV)xHO]/100}
OV (Cool) = CV [(CVxCO)/100]

VARIABLE

PROCESS

SETPOINT

INPUT 2

MANUAL

BUS_ONLY

NONE

= Retransmit the process variable on output 2
= Retransmit the active set-point variable on

output 2

= Retransmit input 2 on output 2
= Manually control output 2 from front panel
= Output 2 is controlled via the computer and

RS-485 Communications

= Fix second output at 0 mA.

PROC HI

or

SETPT HI

xxxx

–3000 to 30000.
Decimal placed per Inputs, Table 2.
Value of the retransmission variable, in
engineering units, which produces the 100%
current on output 2.

PROC LO

or

SETPT LO

xxxx

–3000 to 30000.
Decimal placed per Inputs, Table 2.
Value of the retransmission variable, in
engineering units, which produces the 0%
current on output 2.

MA. HIGH

xx.x

01.0 to 54.0 mA dc
The current produced by 100% output from the
control algorithm.

Example: 100% = 20 mA dc

MA. LOW

xx.x

0 to (mA high – 1) mA dc
The current produced by 0% output from the
control algorithm.

Example: 0% = 4 mA dc