Micromod MOD: Modcell 2050R Users Guide User Manual

Page 75

Advertising
background image

IB-23C650

SETUP

Table 3. Digital Input Setup Menu

Middle

Display

Bottom

Display

Entry Description

LOCKOUT

YES

NO

= Locks out the front panel ramp/soak

commands indicated

R/H,RSET =

Run/hold, reset commands
locked if run/stop selected

RUN/HOLD =

Run/hold commands
locked if run/hold selected

SKIP =

Skip commands locked if
run/skip selected

= Allows all front panel commands to the

ramp/soak algorithm

Also see note in 2.1.2 above.

DI2 FUNC

RUN/STOP

RUN/RSET

RUN/HOLD

= If DI closed: start counting at preset value

If DI open:

reset and stop at preset value

= If DI closed: continue from current count

If DI open:

reset and begin counting from
preset value

= If DI closed: continue from current count

If DI open:

stop and hold current count

LOCKOUT

YES

NO

= Locks out the front panel totalizer

commands indicated

R/H,RSET = Run/hold, reset commands locked

if run/stop selected

RESET =

Reset commands locked if
run/reset selected

RUN/HOLD =

Run/hold commands
locked if run/hold selected

= Allows all front panel commands to the

totalizer algorithm

Also see note in 2.1.2 above.

LOCKOUT

YES

NO

= Locks out the front panel selection of active

set-point

= Allows front selection of active set-point
When both digital inputs are used for set-point
selection, this choice applies to both. They are
not independent.
Also see note 2.1.2 above.