Orion Instruments Eclipse 705 User Manual

Page 23

Advertising
background image

23

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.1 Measurement Type: Level Only (Loop Control = Level)

Display

Action

Comment

33

DispFact
(select)

Select Yes to display factory
parameter menus

34

History

(current status)

Press Enter to view history
of exceptions

Diagnostic Display

35

Run Time

36

History Reset

Press Enter and select yes
to clear history

Similar to SZ Alarm Reset

37

HF cable
(select)

Superuser Parameter

Select from 3-foot or 12-foot remote

38

FidTicks

xxxx

Diagnostic Display

Time of flight from start of ramp to fiducial

39

FidSprd

40

Fid Type
(select)

Superuser Parameter

Select from positive or negative
(Selection only allowed for some probes)

41

Fid Gain

xxx

Superuser Parameter

Amount of gain applied to the fiducial signal

42

Window

xxx

Factory Parameter

43

Conv Fct

xxxx

Factory Parameter

Calibration parameter

44

Scl Ofst

xxx

Factory Parameter

Calibration parameter

45

Neg Ampl

xxx

Superuser Password

Diagnostic parameter

46

Pos Ampl

xxx

Superuser Password

Diagnostic parameter

47

Signal

xxx

Diagnostic Display

Indication of level signal amplitude

48

Compsate
(select)

Superuser Password

Select from None, Manual, Auto

49

DrateFct

xxxx

Diagnostic Display

Compsate = Auto. Velocity derating factor for Model 7xS Steam
probe

50

Targ Ampl

xxxx

Diagnostic Display

Compsate = Auto. Indication of steam reference target amplitude

51

Targ Tks

xxxx

Diagnostic Display

Compsate = Auto. Measured time of flight from fiducial to steam
reference target

52

Targ Cal

xxxx

Diagnostic Display

Compsate = Auto. Calibrated time of flight from fiducial to target
in room temperature air

53

OperMode
(select)

Superuser Password

Compsate = Auto. Select from Run, Cal, Off

54

7xKCorr

xxx

Superuser Password

Distance in mm from fiducial to user reference point
(7xK probe characteristic)

55

ElecTemp

xxx C

Diagnostic Display

Present temperature in electronics compartment
(degrees Celsius)

56

Max Temp

xxx C

Superuser Password

Maximum electronics temperature recorded

57

Min Temp

xxx C

Superuser Password

Minimum electronics temperature recorded

58

SZ Hyst
xx.x lu

Superuser Password

Advertising