3 troubleshooting, 1 troubleshooting system problems — model 705 – Orion Instruments Eclipse 705 User Manual

Page 43

Advertising
background image

43

57-600 Eclipse

®

Guided Wave Radar Transmitter

LEVEL, % OUTPUT and LOOP values

Basic configuration data is

Reconfigure the Probe Model and/or Probe

are all inaccurate.

questionable.

Mount, Probe Length or Level Offset.

1) Ensure the Level is accurate.
2) Verify 4 mA and 20 mA Loop values.

Interface level has significant emulsion. Examine process to reduce/eliminate

emulsion layer.

LEVEL readings are repeatable but

Configuration data does not

Ensure proper Probe Model and probe length.

consistently high or low from actual

accurately match probe length

by a fixed amount.

or tank height.

Adjust trim level value by the amount of
noted inaccuracy.

LEVEL, % OUTPUT and LOOP

Turbulence

Increase the Damping factor until the

values fluctuate.

readings stabilize.

High Frequency connection

Check Fid Spread (should be stable within
±10 counts).

LEVEL, % OUTPUT and LOOP

Lower dielectric material over higher

Select Fixed Threshold option.

values all reading low vs. actual.

dielectric material, e.g., oil over water

Coating, clumping or buildup on probe

These may be expected inaccuracies due
to affect on pulse propagation.

Dense, water based foam

These may be expected inaccuracies due
to affect on pulse propagation.

LEVEL reading on Display is correct

Basic configuration data is

Set POLL ADR to 0 if not using

but LOOP is stuck on 4 mA.

questionable.

HART multi-drop.

HART device only: handheld will only

Most current Device Descriptors

Contact local HART service center for the

read Universal Commands.

(DDs) are not installed in handheld.

latest DDs.

Level Reading on Display is stuck at

Software believes probe is flooded

Check actual level. If probe is not flooded,

full scale, loop is stuck at 20.5 mA.

(level near very top of probe).

Check for buildup or obstructions near top
of probe. Select higher dielectric range.
Check for condensation in probe
connection. Add Blocking Distance.

LEVEL, % OUTPUT and LOOP

Possible configuration issue

1) Increase Blocking Distance

values all at maximum level.

with single rod probe

2) Increase Dielectric Range

LEVEL, % OUTPUT and LOOP

Possible obstruction in tank

1) Increase Dielectric Range until

values all reading high vs. actual.

affecting single rod probe

obstruction is ignored

2) Relocate probe away from obstruction

LEVEL value reading high when

Transmitter loose or disconnected

Ensure transmitter connected securely

should be zero.

from probe

to probe.

Symptom

Problem

Solution

3.3.1 Troubleshooting System Problems — Model 705

NOTE: When consulting the factory concerning improper operation, use proper tables on Pages 66-67. Enter all data when transmitter

is working CORRECTLY or INCORRECTLY.

3.3

Troubleshooting

The ECLIPSE transmitter is designed and engineered for
trouble-free operation over a wide range of operating
conditions. Common transmitter problems are discussed
in terms of their symptoms and recommended corrective
actions. Information on how to handle material buildup
on the probe is also provided in this section.

WARNING! Explosion hazard. Do not connect or disconnect equip-

ment unless power has been switched off or the area is
known to be non-hazardous.