4 measurement type: interface and volume – Orion Instruments Eclipse 705 User Manual

Page 30

Advertising
background image

30

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.4 Measurement Type: Interface and Volume

Display

Action

Comment

1

*Status*
*IfcLvl*

*% Out *
* Loop *

Transmitter Display

LoopCtrl = IfcLevel and Volume
Transmitter default display showing Status, Interface Level,
Volume, % Output,
and Loop values cycles every 5 seconds

2

IfcLevel
xxx.x lu

Transmitter Display

LoopCtrl = IfcLevel

3

Ifc Vol
xxxx vu

Transmitter Display

LoopCtrl = Ifc Vol

4

% Output

xx.x%

Transmitter Display

Transmitter displays % Output measurement derived from
20 mA span

5

Loop

xx.xx mA

Transmitter Display

Transmitter displays Loop value (mA)

6

Level

7

Volume

8

PrbModel
(select)

Select the type of probe
used

(Example: 7xT-x)

Select from 7xB-x, 7xD-x, 7xF-x, 7xG, 7xL, 7xM, 7xN, 7xT-x,
7x7-x
as shown on the probe nameplate

9

PrbMount
(select)

Select the type of probe
mounting

Select from NPT, BSP, or Flange

10

MeasType
(select)

Select type of measurement

Select from Ifc&Vol

11

LvlUnits
(select)

Select level units

Select from cm, inches, feet or meters

12

Probe Ln
xxx.x lu

Enter the exact length of
probe

Probe length is printed on the nameplate and order information
and is the last three digits of the probe model number

13

Lvl Ofst
xxx.x lu

Enter the desired reading
when probe is dry

Offset is the distance from the probe tip to the desired 0 level
point (-90 to 300"). Refer to Section 2.6.6

14

VolUnits
(select)

Select the volume units

Select from liters or gallons
Measure type = Lvl&Vol or Ifc&Vol

15

StrapTbl

nn pnts

Enter to access strapping
table

Measure type = Lvl&Vol or Ifc&Vol

16

Upr Diel
(select)

Enter the dielectric constant
of the upper liquid

Interface mode

17

Dielctrc
(select)

Select range bounding the
dielectric constant of the
lower liquid

Select 10–100

18

Senstvty

xxx

Enter value upward or
downward to sense liquid
surface

Allows fine gain adjustment for single rod probes (this parameter
is password protected for coaxial and twin rod probes)

19

LoopCtrl
(select)

Select variable to control
loop current

Select from Level, Volume, IfcLvl or IfcVol

20

Set 4mA

xxx.x 1u

Enter the PV value for the
4 mA point

A small transition zone (0–6") may exist at the top/bottom of
the probe. See Functional Specifications Probe, Section 3.6.1

21

Set 20mA
xxx.x lu

Enter the PV value for the
20 mA point

A small transition zone (0–6") may exist at the top/bottom of
the probe

22

Damping

xx s

Enter time constant of
desired damping

A Damping factor (0–10 seconds) may be added to smooth the
output due to turbulence

23

Fault

(select)

Select the loop current value
in presence of a fault

Select from 3.6 mA, 22 mA or HOLD