24

57-600 Eclipse

®

Guided Wave Radar Transmitter

2.6.5.2 Measurement Type: Level and Volume (Loop Control = Volume)

Display

Action

Comment

1

*Status*
*Volume*

*% Out *
* Loop *

Transmitter Display

LoopCtrl = Volume
Transmitter default display showing: Status, Volume, % Output
and Loop values cycles every 5 seconds

2

Volume
xxx vu

Transmitter Display

Transmitter displays Volume in selected units

3

% Output

xx.x%

Transmitter Display

Transmitter displays % Output measurement derived from 20 mA
span

4

Loop

xx.xx mA

Transmitter Display

Transmitter displays Loop value (mA)

5

Level

xxx.x 1u

Transmitter Display

Transmitter displays Level Value in selected units

6

PrbModel
(select)

Select the type of probe
used

(Example: 7xR-x)

Select from 7xA-x, 7xB-x, 7xD-x, 7xE-x, 7xF-x, 7xF-E, 7xF-F,
7xF-4, 7xF-P, 7xG-x, 7xJ-x, 7xK-x
, 7xL, 7xM, 7xN, 7xP-x, 7xR-x,
7xS-x, 7xT-x, 7x1-x, 7x2-x, 7x5-x, 7x7-x as shown on the probe
nameplate

7

PrbMount
(select)

Select the type of probe
mounting

Select from NPT, BSP, or Flange

8

MeasType
(select)

Select type of measurement

Select from Lvl&Vol

9

LvlUnits
(select)

Select level units

Select from cm, inches, feet or meters

10

Probe Ln
xxx.x lu

Enter the exact length of
probe

Probe length is printed on the nameplate and order information
and is the last three digits of the probe model number

11

Lvl Ofst
xxx.x lu

Enter desired Level reading
when probe is dry

Level Offset is the distance from the probe tip to the desired 0
level point (-90 to 300"). Refer to Section 2.6.6

12

VolUnits
(select)

Select the volume units

Select from liters or gallons

13

StrapTbl

nn pnts

Enter to access strapping
table

20-point strapping table enables conversion from level to volume
(Refer to Section 2.6.7 for more information)

14

Dielctrc
(select)

Select range bounding the
dielectric constant of the
media

Select from 1.4–1.7; 1.7–3; 3–10; 10–100

15

Senstvty

xxx

Enter value upward or
downward to sense liquid
surface

Allows fine gain adjustment for single rod probes (this parameter
is password protected for coaxial and twin rod probes)

16

LoopCtrl
(select)

Select variable to control
loop current

Select from Level or Volume

17

Set 4mA
xxxx vu

Enter the PV value for the
4 mA point

A small transition zone (0–6") may exist at the top/bottom of
the probe. See Functional Specifications Probe, Section 3.6.1

18

Set 20mA

xxxx vu

Enter the PV value for the
20 mA point

A small transition zone (0–6") may exist at the top/bottom of
the probe

19

Damping

xx s

Enter time constant of
desired damping

A Damping factor (0–10 seconds) may be added to smooth the
output due to turbulence

20

Fault

(select)

Select the loop current value
in presence of a fault

Select from 3.6 mA, 22 mA or HOLD

21

BlockDis

xx.x lu

Enter distance below refer-
ence point where level is not
sensed

Allows user to ignore level measurements near the top of the
probe