INSTALLATION

15

Distance (ft.)

Number of Pipe Supports

16 2
32 3
48 5
64 7
80 9


C.3.1. Installation At The Same Level

If the condensing unit is going to be installed at the same level with the cabinet, follow the instructions in the FIG #5

FIG # 5
















C.3.2. Installation At Different Levels

If the remote condensing unit is installed at a higher level than the cabinet (FIG #6) insert a siphon in the return

line at every 6 ft. of difference in height. If the remote condensing unit is installed at a lower level than the cabinet (FIG #7)
it is not necessary to insert any siphons.

FIG #6

FIG #7

Insert a siphon at the beginning (a) and at the end (b) of each riser