Recover/Recycle/Recharge Unit

29

Maintenance

The unit keeps track of the filter-drier’s remaining capacity. As the unit filters
refrigerant, the remaining capacity decreases from 68 kg (150 lbs.) to zero.
When the capacity reaches zero, the unit will display:

Use the following steps to reset the filter-drier’s capacity.

1. Plug the power cord into a correct voltage outlet.

2. Press the Arrow keys simultaneously until UNITS KG (LBS) appears on

the display.

3. Press the Menu key (

) until FILTER XXX appears on the display.

4. Press the Arrow keys simultaneously until FILTER 68KG (150 LBS)

appears on the display.

5. Press the Menu key (

) until EXIT displays.

6. Press the Start/Stop key ( ) to exit the diagnostics function.

The unit is now ready to begin counting down for the new filter-drier.