6.0 Maintenance & Handling

6.1

Count/Hour Meter (Dual Speed Only)

6.1.1

Dual Speed

 On dual speed trolleys, the VFD has a Count/Hour function built into the parameters. Refer to

Table 6-1 for parameter identification. Refer to Table 6-2 for Count/Hour access procedure.

Table 6-1 VFD Count/Hour Parameter Identification

Parameter

Name

Discription

U7-01

Number of Starts

(Higher Order)

The number of starts in the down direction x 1,000. Up to 10,000 units are displayed.

Display of “1” = 1,000 starts.

Display of “10,000” = 10,000,000 starts

U7-02

Number of Starts

(Lower Order)

The number of starts in the down direction under 1,000 starts (1 to 999). One start
will register a “1” in the display. When 1,000 starts are reached, the value of U7-01 is
incremented by 1 and the value of U7-02 is reset to 0.

U7-03

Hours of

Operation

The number of hours of operation in both the up and down directions. One hour will
register a “1” in the display. Up to 65535 hours are displayed.

 Example using Table 6-1:

U7-01 displays “81”, U7-02 displays “567”, U7-03 displays “122”

Number of Starts (down) = 81,567

Number of Operated Hours = 122

Table 6-2 VFD Count/Hour Access Procedure

Operational Step

VFD Display

1. Energize the hoist.

2. Press

until the “Monitor” screen is displayed (blinking).

3. Press

to display the parameter setting screen an then press

to move from

“01” to “U1”.

4. Press

or

until the display reads “U7” (left value blinking).

5. Press

and

or

to select the specific “Monitor” parameter (right vlaue

blinking).

(Example: U7-03 –Hours of Operation)

6. Press

to display the current parameter value.

(Example: 75 Hours)

7. Press

until the diplay returns to the initial screen.

(As in Step 1.)