1.12.2 Chart Recording Rate

This function controls how frequently the detector and alarm level or flow rates are stored in the FIRElink-
100’s internal chart recorder log (see section 1.14, ‘Chart Recording’ on page 18).

Setting

Type

Storage Interval

Time per Division on Chart Log

0

Detector Output

1 second

10 seconds

1

Detector Output

5 seconds

50 seconds

2

Detector Output

12 seconds

2 minutes

3

Detector Output

30 seconds

5 minutes

4

Detector Output

1 minute

10 minutes

5

Detector Output

2 minutes

20 minutes

6

Detector Output

5 minutes

50 minutes

7

Detector Output

10 minutes

100 minutes

8

Detector Output

20 minutes

200 minutes

9

Detector Output

50 minutes

500 minutes

10

Flow Recording

1 second

10 seconds

11

Flow Recording

5 seconds

50 seconds

12

Flow Recording

12 seconds

2 minutes

13

Flow Recording

30 seconds

5 minutes

14

Flow Recording

1 minute

10 minutes

15

Flow Recording

2 minutes

20 minutes

16

Flow Recording

5 minutes

50 minutes

17

Flow Recording

10 minutes

100 minutes

18

Flow Recording

20 minutes

200 minutes

19

Flow Recording

50 minutes

500 minutes

In the above table the shaded cells indicate flow rate recording whilst the white cells indicate detector and
alarm level recording.

At the slowest recording rate, one month of data can be recorded. The factory default setting is 8.

1.12.3 Separator

Condition

The value given at this function is the efficiency rating of the dust separator element in the detector as a
percentage of the efficiency of a clean separator. A new element will give a reading of 99 in this function.
When the efficiency has decreased to 80%, the Fault indicator LED will illuminate and the event log will
show “Separator renew”.

NOTE: Fitting a new element will reset this figure to 99

1.12.4 Separator Change Date

This function defaults to “--“, which means that a separator fault will only appear when the efficiency
decreases to 80% (see 1.12.3, “Separator Condition”). However, a date may be entered into this function