FIRElink-100 – Installation Manual

© 2010 Hochiki Europe (UK) Ltd

9-5-0-345/ISS4/OCT10

4.3 Connecting a FIRElink-100 to an addressable Fire Panel

An Addressable Programmable Interface Card (FIRElink-APIC) may be used to decode detector
information and to relay this to a Fire Panel.

The FIRElink-APIC is fitted to the four mounting studs on the FIRElink-100 PCB using the supplied
screws as shown below:

FIRElink-APIC

Mounting Studs

(x 4)

FIRElink-APIC

Address Switches

(x 2)

FIRElink-APIC

Interface

Connection

The connections to the Fire Panel are made using the BUS L1 and H1 (bus 1 input and output) and the
BUS L2 and H2 (bus 1 input and output) terminal connectors shown in Section 3.1.4.

The only settings that need to be made are on the FIRElink-APIC address DIP switches. The start loop
address Is entered on SW1 and the end loop address on SW2. In the case of a single FIRElink-100 the
start and end addresses will be the same.