FIRElink-100 – Installation Manual

© 2010 Hochiki Europe (UK) Ltd

9-5-0-345/ISS4/OCT10

10 FIRElink-100 Specification

SELV Rating (EN 60950)

Class III

Supply Voltage

21.6Vd.c. - 26.4Vd.c.
PSU Type: conforming to EN 54-4 Electrical safety complies with
BS EN 610190-1

Size (mm)

300W x 220H x 85D

Weight

3.8kg with docking station

Operating Temperature Range

0 to +38°C (UL268)
-10 to +60°C (CEA4022)

Operating Humidity Range

0 - 90% Non Condensing
BS EN 61010-1 Pollution degree 1
BS EN 61010-1 Installation Cat. II
0.03% to 25% Full Scale Deflection (FSD)

Measurement Range (obs/m)

0.0015% to 25% Sensitivity Resolution

Detection Principle

Laser light scattering mass detection

Particle Sensitivity Range

0.0003µm to 10µm

Current Consumption

400mA @ 24Vd.c.

Relay Contact Rating

500mA @ 30Vd.c.

Maximum Sampling Pipe Length

100 metres total (see section 2 "Design Limitations" on page 20)

Sampling Pipe Inlets

2

Sampling Pipe Internal Diameter

15-25mm

Alarm levels

2 – "FIRE" and "FAULT" (2 additional levels available with
optional Relay Card or FIRElink-APIC fitted)

Chamber Service Intervals

Greater than 8 years (depending on environment)

Dust Separator Replacement Intervals Greater than 5 years (depending on environment)
Laser Lifetime (MTTF)

Greater than 1000 years

Programming PC

via

RS232/RS485

Data Bus Cable

RS485 data cable

Data Bus Length

1.2 km

IP Rating

IP50

NOTE: This equipment is only to be used in accordance with this specification. Failure to operate the

equipment as specified may cause damage to the unit.