Hochiki FIRElink-100 User Manual

Page 36

Advertising
background image

Page 36 of 40

FIRElink-100 – Installation Manual

© 2010 Hochiki Europe (UK) Ltd

9-5-0-345/ISS4/OCT10

Click on the list entry to highlight it and click on the Diagnostics button. The software will then
commence the system tests. During the “Aspirator and flow” test, the detector fan will suddenly slow
down, but this is a normal part of the test.

When the test has finished and no problems have been found, the following screen is displayed:

If any problems were found during the diagnostic tests, the nature of the fault will be indicated in the
“Status” column.

Scan:

Reads in the status of all connected detectors.

Read Button: This brings up a display of the detector output and flow rate which updates in real time.

Relays:

Brings up a screen allowing the function of the volt-free ‘Fire’ and Fault LEDs to be tested

with the aid of a continuity meter or other tester. The Fire relay contacts are open in

normal operation and will close on test. The Fault relay contacts operate on a ‘Fail-safe’

basis and are held closed in normal operation. They will therefore open on test.

Save As:

Saves the summary list of scanned detectors and their status as a text (.txt) file.

Print:

Prints the summary list to a connected printer.

Advertising