Part 1 Installation

Chapter 3 Installation and W

iring

25

Part 1 Installation

(3) Noise sources and noise elimination

There are many noise sources, but solenoid valves, magnet switches and relays are of particular

concern when building a system. Noise from these parts can be eliminated using the measures

specified below:

[1] AC solenoid valve, magnet switch, relay

Measure --- Install a surge killer in parallel with the coil.

[2] DC solenoid valve, magnet switch, relay

Measure --- Install a diode in parallel with the coil. Determine the diode capacity in accordance with

the load capacity.

In a DC circuit, connecting a diode in reversed polarity will

damage the diode, internal parts of the controller and DC

power supply. Exercise due caution.

The above noise elimination measures are particularly important when a 24-VDC relay is driven

directly by a controller output and there is also a 100-VAC solenoid valve, etc.

Surge killer

m

Point

Wire from each coil over the shortest distance.

Installing a surge killer on the terminal block, etc.,

will be less effective because of a longer distance

from the coil.

Diode