TTRA-S2 VERSION 1.x SOFTWARE MANUAL

REV 2

43

6.2

Running a Transformer Test Using the Create Test Option

The Create Test option from the Test-Xfmr menu can be used to quickly create a test plan for
running a test. To test a transformer using the Create Test option:

1. From the Test-Xfmr menu, click on Create Test and then select Transformer.

NOTE

You can also select Load Tap Changer or Voltage Regulator to create a Load
Tap Changer or Voltage Regulator test respectively. You will then be asked
for the relevant parameters for the test. Please see sections 5.9.2 and 5.9.3
for further information.

An untitled test plan will be displayed as shown below:

2. Fill in the header information.

3. Select the transformer type and group, if applicable, from the corresponding drop-down

lists.

4. Edit the Max. Dev. % value if necessary.

5. Select the test voltage from the “Voltage:” drop-down list.

6. Fill in the transformer nameplate voltages. The “Phase” and “Calc. Ratio” fields will be

filled in automatically.

7. Click on the “Run Test”, “Next Test” or “Repeat Test” button to test the transformer.