0 using the transformer turns ratio calculator – Vanguard TTRA-S2 (ATRT-03 S2, ATRT-03A S2, ATRT-03B S2, Tri-Phase) User Manual

Page 48

Advertising
background image

TTRA-S2 VERSION 1.x SOFTWARE MANUAL

REV 2

45

7.0 USING THE TRANSFORMER TURNS RATIO CALCULATOR

The TTRA-S2 software features a turns ratio calculator that can be used to quickly calculate the
winding turns ratio of a transformer. To use the calculator:

1. Click on the File menu and select Calculator. The calculator window will be displayed as

shown below:

2. Type the H voltage and X voltage values in the corresponding fields.

3. Select the transformer type from the “Type:” drop-down list.

4. If desired, type a percentage value in the “Percent:” input field. This option calculates

the turns ratio at the specified percentage of the nameplate voltage. For example, if the
H nameplate voltage is 12,000V, the X nameplate voltage is 1200V, the transformer type
is single phase, and the percentage value of 80 is used, the turns ratio will be calculated
as:

Ratio = (V

H

/ V

X

) x (Percent / 100)

= (12,000 / 1200) x (80 / 100)

=

8.00

5. Click on the “Calculate” button and the calculated ratio will be displayed to the right of

the “Ratio:” label.

Advertising