Vanguard CT-6500 S2 User Manual

Page 11

Advertising
background image

CT-6500 Series 2 Operating Instructions

10

NOTE

The CT-6500 can detect insertion resistors ranging from 10 to 7,000 Ohms.
Resistances over 7,000 Ohms are detected as an open contact.


3.2 Mechanical Measurement Results

In the Time Travel Mode, the digital transducer channels provide the following test results:

- CB contact stroke
-

CB

contact

over

travel

-

CB

Contact

bounce

back

-

CB

Contact

wipe

- CB Contact velocity

Breaker contact speed calculations are based upon a contact's travel distance over a period of

time, which is defined by the manufacturer's specifications.

NOTE

When the resistor type transducer channel is used, the test results are shown as
transducer channel 1.
CB contact mechanical measurement can be shown in “English” or “Metric” units.

3.3 Analog Voltage Input Results

The analog voltage, input channel, “V1” measures the breaker's DC control voltage during an

operation. Printed voltage readings include nominal voltage (when the supply voltage has no
load) and minimum voltage (when the supply voltage is under load or when a coil is energized).
The “V1” connection allows the user to monitor the DC power supply’s voltage fluctuations during
a breaker operation. This feature is effective in detecting breaker power supply problems, which
normally can not be seen by using a voltmeter.

NOTE

Printed voltage readings can range from 0 to 255Vdc.


3.4 Digital Voltage Input Results

The digital voltage, input channel, “V2” monitors the voltage status as “ON” or “OFF”

conditions and graphs the result. A voltage level above 30Vdc is considered as the “ON” state.
The input channel is dedicated to monitor the breaker’s auxiliary switch action during a breaker
operation.

NOTE

The input voltage ranges from 0 to 300Vdc or peak ac.


3.5 Initiate Current Results

The CT-6500 not only plots the trip or close current waveforms, but also prints the steady-state

current readings of the trip and close coils during an operation. A typical circuit breaker timing
report is shown in Figure 11.0.

Advertising