9.1.1 Timing an OPEN Operation (With No Insertion Resistors)
The following example shows the steps for performing an Open Test on a circuit breaker.

Table 3.0 Open Operation With No Insertion Resistors

STEP OPERATION

ACTION DISPLAY

1

READY TIMER FOR BREAKER OPERATION..

PRESS #1 KEY.

INSERTION RESISTOR?

1.NO

2.YES

2

SELECT NO INSERTION RESISTOR.

PRESS #1 KEY.

TIMING WINDOWS:

1.WINDOW = 1 SEC

2.WINDOW = 10 SEC

3. WINDOW = 20 SEC

3

SELECT 1-SECOND TIMING WINDOW.

PRESS #1 KEY.

TRIGGER MODE:

1. INTERNAL TRIGGER

2. EXTERNAL TRIGGER

4

SELECT INTERNAL TRIGGER.

PRESS #1 KEY.

TIMING MODE:

1. OPEN

2. CLOSE

3.

O-C

4.

C-O

5. O-C-O

5

SELECT OPEN OPERATION.

PRESS #1 KEY.

OPEN TIMING

Hold "ARM" Switch,

Then "START".

"STOP" to ABORT

6

INITIATE OPEN COMMAND.

HOLD THE "ARM"

SWITCH AND

PRESS THE "START"

KEY.

TEST IN PROGRESS

Hold "ARM" Until

Test complete.

(Up to 25 seconds)

7

OBSERVE BREAKER OPERATED.

ANALYZER IS READY TO OUTPUT RESULTS.

NONE.

1.RUN TEST 06/12/07

2.GET RSLT 19:20:01

3.SET-UP

4.DIAGNOSTIC

Go to section 9.2 to print a test report.

NOTE

One-second timing windows are used for breaker timing. The 10 and 20 second
timing windows are used for long timing events (i.e. timing circuit-switchers).
The user can set the CT-6500 to print tabulated and graphical reports
automatically after it completes a test. See Paragraph 9.17 for the automatic print
setting.