Vanguard CT-6500 S2 User Manual

Page 16

Advertising
background image

CT-6500 Series 2 Operating Instructions

15

6.0 CT-6500 Analyzer Specifications


PHYSICAL SPECIFICATIONS

16” W by 11”H by 14”D (40.6 cm x 29.9 cm x 35.6 cm)

Weight: 25lbs (11.3Kg).

INPUT POWER

8 Amperes, 90-120Vac or 200-240Vac (selectable), 50/60 Hz.


DRY-CONTACT INPUT

3 or 6 or 12 contact channels. All contact inputs are grounded until testing

is started. Each contact detects main and insertion resistor contacts.


TIMING WINDOW

Selectable between: 1, 10, or 20 second.


TIMING RESOLUTION

±50 microseconds at 1 second duration.

±0.5 millisecond at 10 second duration.

±1.0 millisecond at 20 second duration.


TIMING ACCURACY

0.05% of reading,

±50 micro-seconds at 1-second duration.



CONTACT DETECTION RANGE

CLOSED: less than 20 Ohms.

RANGE

OPEN: greater than 10,000 Ohms.


RESISTOR DETECTION RANGE

Ranges from 50 to 5,000 Ohms.


EXTERNAL TRIGGER INPUT

Open/Close: 30 to 300Vdc, peak Vac.


VOLTAGE SENSING INPUTS

V1: analog input, 0-255V dc or peak ac. Sensitivity:

±1V;

V2: voltage detector (present/absent).Input: 30-300V, dc or peak ac.


BREAKER OPERATION

Open, Close, Open-Close, Close-Open, and Open-Close-Open.


BREAKER INITIATE CAPACITY

30A/250V ac/dc max (100A inrush).


INITIATE CURRENT READING

One, Non-contact, hall-effect sensor ranging from 0-20 Amperes, DC to 5 kHz.

RANGE

TRAVEL TRANSDUCER

3 travel-transducer channels. Linear motion from 0.0 to 30.0 inches (±0.01) inch.

INPUT

Rotary ranges from 0 to 360

o

(± 0.36º).

BREAKER SLOW-CLOSE

Measures “Slow-Close” the contact point distance (hard copy printout).

TEST

DISPLAY

Back-lit LCD screen, 4-lines by 20-characters, sunlight viewable.


PRINTOUT

Both graphic contact-travel waveforms & tabulated results are printed on 4.5 inch
thermal paper.


STORAGE CAPABILITIES

Store up to 100 timing records.


COMPUTER INTERFACE

RS-232C Port, USB Port.


PC SOFTWARE (included)

Furnished Circuit Breaker Analyzer PC software. Windows XP and Windows Vista

compatible. The analysis software can be installed on an IBM-compatible computer

for graphical display, numerical reports and database utility for office use.


SAFETY

Designed to meet UL 61010A-1 Certification and CAN/CSA C22.2 No 1010.1-92.