Vanguard CT-6500 S2 User Manual

Page 59

Advertising
background image

CT-6500 Series 2 Operating Instructions

58

9.15 Check Cable Hookup

The following steps allow the user to check the CT-6500 contact cable connections to the
circuit breaker.

Table 20.0 Checking the Cable Hookup

STEP OPERATION

ACTION

DISPLAY

1

SELECT DIAGNOSTIC.

PRESS # 4 KEY.

1. SLOW-CLOSE TEST

2. CHECK HOOKUP

3. TEST TRANSDUCER

4. NEXT PAGE

2

SELECT CHECK HOOK UP.

PRESS # 2 KEY.

MAKE SURE BREAKER

IS IN CLOSE POSITION,

THEN PRESS "START"

3

INITIATE TEST.

PRESS THE "START"

KEY.

1 2 3

C - - -

“START” to RETEST

“STOP” to EXIT

4

RETURN TO MAIN MENU.

PRESS THE "STOP"

KEY.

1.RUN TEST 06/10/07

2.GET RESULTS 20:10:01

3.SETUP

4.DIAGNOSTIC

NOTES

1. The CT-6500 will also print a test report with the thermal printer.

2. A contact closure is shown as "C" on the LCD and printout.

3. An open contact is shown as "-" on the LCD and printout.

Advertising