Structural specifications – Proface GP4100 - 3.4 Compact HMIs" User Manual

Page 32

Advertising
background image

Chapter 3 Specifications

3-3

Structural Specifications

Electrical

Noise Immunity

Noise Voltage: 1,000 Vp-p
Pulse Duration: 1 µs
Rise Time: 1 ns, (via noise simulator)

Noise Immunity
(Fast Transient Burst Noise)

Power Line: 2 kV (IEC/EN61000-4-4)
COM Port (Excluding GP4104): 1 kV (IEC/EN61000-4-4)

Electrostatic Discharge
Immunity

Contact Discharge Method: 6 kV/Air Discharge Method: 8 kV
(IEC/EN61000-4-2 Level 3)

*1

When using in an environment where the temperature becomes or exceeds 40°C for an

extended period of time, the screen contrast level may decrease from its original level of

brightness.

Inst

all

ation

Grounding

Functional grounding:Grounding resistance of 100

, 2mm

2

(14 AWG) or thicker wire, or your country’s applicable
standard. (Same for FG and SG terminals)

Structure

*1

*1

The front face of the GP unit, installed in a solid panel, has been tested using, conditions
equivalent to the standards shown in the specification. Even though the, GP unit’s level of
resistance is equivalent to these standards, oils that should have, no effect on the GP can
possibly harm the unit. This can occur in areas where either, vaporized oils are present, or
where low viscosity cutting oils are allowed to adhere, to the unit for long periods of time. If
the GP’s front face protection sheet becomes, peeled off, these conditions can lead to the
ingress of oil into the GP and separate, protection measures are suggested.
Also, if non-approved oils are present, it may cause deformation or corrosion of the, front
panel’s plastic cover. Therefore, prior to installing the GP be sure to confirm the, type of
conditions that will be present in the GP’s operating environment.
If the installation gasket is used for a long period of time, or if the unit and its gasket, are
removed from the panel, the original level of the protection cannot be guaranteed. To
maintain the original protection level, be sure to replace the installation gasket regularly.

IP65f NEMA #250 TYPE 4X/13
(on the front panel when properly installed in an enclosure)

Installation Configuration

Embedded panel

Cooling Method

Natural air circulation

Weight Approx.

0.2 kg [0.4 lb] or less (display unit only)

External Dimensions

W116.5 x H77.5 x D28 mm [W4.59 x H3.05 x D1.1 in.]

Panel Cut Dimensions

W105 x H66 mm [W4.13 x H2.6 in.]

*2

Panel thickness area: 1 to 5 mm [0.04 to 0.2 in.]

*3

*2

Regarding dimensional tolerance, everything +1/-0 mm [+0.04/-0 in.] and R in angle are
below R3 [R0.12 in.].

*3

Even if panel thickness is within recommend range for “Panel Cut Dimensions”, the panel
could warp, depending on panel’s material, size, and installation location of GP or other
devices. To prevent panel warpage, the installation surface may need to be strengthened.

Advertising