Chapter 3 Specifications

3-7

‹Communications Cable Specifications

‹Wiring the COM Interface Connector

(1)

Remove the COM I/F connector from the GP.

(2)

Use a flat-blade screwdriver (Size 0.4 x 2.5) to loosen the terminal screws.

(3)

Strip the communications cable, and attach it to the terminal connector.

(4)

Use a flat-blade screwdriver to tighten the appropriate terminal screws on the terminal connector from

step 3.

(5)

Insert the connector into the GP unit’s serial interface.

Communications
Cable Diameter

*1

*1

When inserting two wires into one terminal connec-

tor, the simple wire diameter is 0.08 to 0.5mm

2

(28 -

22 AWG), and the stranded wire diameter is 0.08 to

0.75mm

2

(28 - 20 AWG).

0.14 to 1.5mm

2

(28 - 16 AWG)

Conductor Type

Simple or Stranded Wire

*2

*2

If the Conductor’s end (individual) wires are not

twisted correctly, the end wires may either short

against each other, or against an electrode.

Conductor Length

• Always ensure that the connector has been removed from the GP unit before wiring

the connector. Failure to do so may result in electric shock.

• The torque required to tighten these screws is 0.196N

•m (1.735[Lb•in]).

7 mm
[0.28 in]

(2)
Use a flat-blade
screwdriver to loosen
the terminal screws.

(4)
Use a flat-blade
screwdriver to tighten
the terminal screws.

(3)
Insert the wire into the
terminal connector.

Terminal Connector