Proface LT3300 - 5.7 All-in-One HMI" User Manual

Page 76

Advertising
background image

Chapter 4 Installation and Wiring

4-9

Connecting the Power Cord

(1) Confirm that the power cord is unplugged from the power supply.

(2) Strip the membrane of the power cord, twist the wire ends, and connect them to the Power Connector

(Plug).

(3) Reattach the Power Connector (Plug).

• Be sure to remove the connector from the LT unit prior to starting wiring. Failure

to do so may cause an electric shock.

• The temperature rating of field installed conductors: 75°C only.

• Use a flat-blade screwdriver (Size 0.6 X 3.5) to tighten the terminal screws.

The torque required to tighten these screws is 0.5 to 0.6N

•m [5-7lb•in].

• Do not solder the cable connection.

• Be sure to twist the power cords together, up to the power connector.

Power Connector
(Socket)

Bottom

Power Connector (Plug)

+

FG

<LT-3201A>

Advertising
This manual is related to the following products: