Chapter 4 Installation and Wiring

4-15

„

Interlock Circuit 2

If there is a possibility that the abnormal operation of the LT may lead to an accident, design a fail-safe

measure to configure an interlock circuit with external hardware devices.

For a system which requires the running motor to stop before all other processes when the travel limit switch

is activated, never design a system in which the signals from the travel limit switch are input to the input

terminals of the LT and then processed using software.

Configure a circuit that reliably stops the running motor using hardware as shown below.

• After executing an internal program, the LT outputs ON/OFF information to the output

devices at the same time. For example, the electromagnetic switches for forward and

reverse rotation of a motor are turned on and off at the same time.

Consequently, a situation may arise in which both of the main contacts of the motor cir-

cuits for the electromagnetic switches for forward and reverse rotation may turn on, caus-

ing a short-circuit of the R and T phases. To avoid this situation, you need to provide the

interlock circuit shown above or use an electromagnetic switch equipped with a mechani-

cal interlock for a forward/reverse circuit.

LT

Running motor control signal

Travel limit switch

Running motor
control circuit

Emergency
stop switch

Travel limit
switch

Direct input to the emer-
gency stop circuit of the
control unit