Operations page / pid 1 menu – Watlow Series 96 User Manual

Page 33

Advertising
background image

Active if Propband 1(PID 1 Menu)

is not set to

[```0], Units Type

(Global Menu) is set to

[``US]

and Operations Page Lock
(Lockout Menu) is not set to
[hide].

502 r/w

0.00 (0)

0.00 to 99.99 repeats

per minute

[rE`1] Reset 1

Set the reset time in
repeats/minute for
output 1.

Active if Propband 1(PID 1 Menu)

is not set to

[```0], Units Type

(Global Menu) is set to

[``SI]

and Operations Page Lock
(Lockout Menu) is not set to
[hide]

.

501 r/w

0.00 (0)

0.00 to 99.99 minutes

per repeat

[It`1] Integral 1

Set the integral time
in minutes for out-
put 1.

Active if Operations Page Lock

(Lockout Menu) is not set to
[hide]

.

500 r/w

25°F, 14°C

0° to 9999°
If

[Pb`1] is set to 0 op-

erates in on/off mode.

[Pb`1] Propband 1

Set the proportional
band for PID con-
trol.

[Pid1]

PID 1 Menu

[Oper] Operations Page

Active if Operations Page (Lock-

out Menu) is not set to

[hide]

.

605 r/w

0

-1999 to 9999

[CAL1] Calibration Offset

Set the input 1 cali-
bration offset.

Active if Input 2 (Input 2 Menu)

is not set to

[`Off], Input 2 is

not set to

[E`In] (event input)

and Operations Page Lock
(Lockout Menu) is not set to
[hide]

.

316 r/w

[```L] (0)

[```L] local (0)
[~~~r] remote (1)

[`L-r] Local or Remote

Mode**

Set the mode to local
or remote set point.

Active if output 2 is present (not

96 _ _-_ A _ _-_ _ _ _), both Out-
put 1 (Output 1 Menu) and
Output 2 (Output 2 Menu) are
set to either

[heat] or [COOL]

and Operations Page Lock
(Lockout Menu) is not set to
[hide].

319 r/w

75°F, 24°C

Range Low 1 to Range

High 1

[`SP2] Set Point 2**

Set the boost set
point.

Active if Input 2 (Input 2 Menu)

is set to

[e`In] (event input),

[E`Fn] is set to [``SP], and
Operations Page Lock (Lockout
Menu) is not set to

[hide].

306 r/w

75°F, 24°C

Range Low 1 to Range

High 1

[E`SP] Event Set Point2**

Set the set point
when the event
input is active as de-
fined by Event Con-
dition.

Active if Operations Page Lock

(Lockout Menu) is not set to
[hide].

304 r/w

90

50 to 150

[AtSP] Auto-tune Set

Point

Set the auto-tune set
point as a percent of
the currently active
set point.

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

Wa t l o w S e r i e s 9 6

P a r a m e t e r s

6 . 3

Operations Page / PID 1 Menu

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.

Advertising