Setup page / global menu – Watlow Series 96 User Manual

Page 47

Advertising
background image

Added if ramping version of the

controller is selected
(96__-____-AA__).

1208 r/w

[``ti] (0)

[``ti] time based (0)
[rate] rate based (1)

[ptyp] Program Type*

Select whether the
program type will be
time based or rate
based.

Appears if Setup Page Lock

(Lockout Menu) is not set to
[hide].

904 r/w

[`OFF] (0)

[`OFF] off (0)
[``on] on (1)

[OPLP] Open Loop

Detect
Turn the open loop
detect feature on or
off.

Active if Local or Remote Mode

(User Menu) is not set to
[```r] , Ramping Mode is not
set to

[`OFF] and Setup Page

Lock (Lockout Menu) is not set
to

[hide].

1101 r/w

10.0 (1)

0.1 to 99.9 (1 to 999)

[rAtE] Ramp Rate**

Set the units or de-
grees set point ramp
rate.

Active if Local or Remote Mode

(User Menu) is not set to
[```r], Ramping Mode (Global
Menu) is not set to

[`Off] and

Setup Page Lock (Lockout
Menu) is not set to

[hide].

1102 r/w

[Min] (0)

[Min] minute (0)
[hour] hour (1)

[rp`S] Ramp Scale**

Set the single step
ramp scaling in de-
grees per hour or
minute.

Active if Local or Remote Mode

(User Menu) is not

[```r] (re-

mote set point is not active)
and Setup Page Lock (Lockout
Menu) is not set to

[hide].

1100 r/w

[`OFF] (0)

[`OFF] off (0)
[Strt] startup only (1)
[Stpt] startup or set

point change (2)

[``rP] Ramping Mode**

Set the single step
ramp to set point
mode.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

715 r/w

100.0 (1000)

0.0 to 100.0 (0 to 1000)

Applies to heat or cool.

[PL`b] High Power Limit

Below

Set high power limit
below the power
limit set point.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

714 r/w

100.0 (1000)

0.0 to 100.0 (0 to 1000)

Applies to heat or cool.

[PL`A] High Power Limit

Above

Set high power limit
above the power
limit set point.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

713 r/w

[rh`1] (1)

[rL`1] Sensor Range

Low

[rh`1] Sensor Range

High

[PLSP] Power Limit Set

Point

Set point for power
limits,

[PL`A] above

this point,

[PL`b]

below.

Wa t l o w S e r i e s 9 6

P a r a m e t e r s

6 . 1 7

Setup Page / Global Menu

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.