Operations page / pid 1 menu – Watlow Series 96 User Manual

Page 34

Advertising
background image

Active if output 2 is present (not

96 _ _-_ A _ _-_ _ _ _), one out-
put is set to

[heat], another is

set to

[COOL] and Operations

Page Lock (Lockout Menu) is
not set to

[hide].

505 r/w

0

0 to 9999

[db`1] Dead Band 1

Set point shift for
output 1 control.

Active if output 1 is not a process

type (not 96 _ _-F _ _ _-_ _ _ _),
Propband 1 (PID 1 Menu) is set
to

[```0] and Operations Page

Lock (Lockout Menu) is not set
to

[hide]

.

507 r/w

3°F, 2°C

1 to 9999

[hys1] Hysteresis 1

Sets the switching
hysteresis for output
1.

Active if Propband 1 (PID 1

Menu) is not set to

[```0],

Burst 1 (PID 1 Menu) is set to
[``no], output 1 is not a pro-
cess type (not 96 _ _-F _ _ _-_ _
_ _) and Operations Page Lock
(Lockout Menu) is not set to
[hide].

506 r/w

Determined

by output
type.

Relay: 5.0 to 60.0 (50 to

600)

Solid State: 0.1 to 60.0

(1 to 600)

[Ct`1] Cycle Time 1

Set the cycle time in
seconds for output 1.

Active if Propband 1 (PID 1

Menu) is not set to

[```0], and

Operations Page Lock (Lockout
Menu) is not set to

[hide], and

if output 1 is equipped for a
solid-state relay (96A _-K _ _ _-
_ _ _ _) or switched dc (96A _-C
_ _ _-_ _ _ _) and high voltage
power supply (96A _-_ _ _ _-_ _
_ _.)

509 r/w

[``no] (0)

[``no] no (0)
[`Yes] yes (1)

[brs1] Burst 1

Select burst fire
mode for output 1.

Active if Propband 1(PID 1 Menu)

is not set to

[```0], Units Type

(Global Menu) is set to

[``US]

and Operations Page Lock
(Lockout Menu) is not set to
[hide].

504 r/w

0.00 (0)

0.00 to 9.99 minutes

[rA`1] Rate 1

Set the rate time in
minutes for output 1.

Active if Propband 1(PID 1 Menu)

is not set to

[```0], Units Type

(Global Menu) is set to

[``SI]

and Operations Page Lock
(Lockout Menu) is not set to
[hide]

.

503 r/w

0.00 (0)

0.00 to 9.99 minutes

[dE`1] Derivative 1

Set the derivative
time in minutes for
output 1.

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

6 . 4

P a r a m e t e r s

Wa t l o w S e r i e s 9 6

Operations Page / PID 1 Menu