Setup page / output 2 menu – Watlow Series 96 User Manual

Page 41

Advertising
background image

Active if output 2 is present, but

is not process type ( not 96 _ _-
_ A _ _-_ _ _ __ or 96 _ _-_ F_ _-
_ _ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

719 r/w

[Proc] (0)

[Proc] process alarm

(0)

[``de] deviation alarm

(1)

[AtY2] Alarm 2 Type

Select alarm type.
A process alarm re-
sponds when the
temperature leaves
a fixed range.
A deviation alarm
responds when the
temperature devi-
ates from the set
point by a set num-
ber of degrees.

Active if output 2 is equipped for

a process (96 _ _-_ F_ _-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to

[hide].

718 r/w

[4-20] (0)

[4-20] 4-20mA (0)
[0-20] 0-20mA (1)
[`0-5] 0-5VÎ (dc) (2)
[`1-5] 1-5VÎ (dc) (3)
[0-10] 0-10VÎ (dc) (4)

[Prc2] Process 2 Type

Sets output 2
process type.

Active if output 2 is present (not

96 _ _-_ A _ _-_ _ _ _) and
Setup Page Lock (Lockout
Menu) is not set to

[hide].

*Event output is added if ramp-

ing version of the controller is
selected (96__-____-AA__.)

717 r/w

[`OFF] (0)

[`OFF] off (0)
[heat] heat (1)
[COOL] cool (2)
[``al] alarm (3)
[eunt] event (4)*

[Ot`2] Output 2

Select output 2
function.

[Out2]

Output 2 Menu****

[`set] Setup Page

Active if output 1 is equipped for

a process (96 _ _-F _ _ _-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to

[hide].

701 r/w

[4-20] (0)

[4-20] 4-20mA (0)
[0-20] 0-20mA (1)
[`0-5] 0-5VÎ (dc) (2)
[`1-5] 1-5VÎ (dc) (3)
[0-10] 0-10VÎ (dc) (4)

[Prc1] Process 1 Type

Sets process 1
output type.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

700 r/w

[heAt] (0)

[heAt] heat (0)
[COOL] cool (1)

[Ot`1] Output 1

Select whether the
control output will
control for heating
or cooling.

[Out1]

Output 1 Menu****

[`set] Setup Page

Active if

[E`fn] is set to

[absp].

1211 r/w

75°F, 24°C

[`Off],
Range Low 1 to Range

High 1 (-32768)

[absp] Abort Set Point

Active if input 2 hardware is pre-

sent (96 _1 _-_ _ _ _ -_ _ _ _),
Input 2 (Input 2 Menu) is set
to

[E`In] (Event Input), Event

Function (Input 2 Menu) is not
set to

[none] and Setup Page

Lock (Lockout Menu) is not set
to

[hide].

1061 r/w

[``LO] (0)

[``LO] low (0):
[``hi] high (1)
[rise] rise (2)
[FALL] fall (3)

[E`cn] Event Condition

Select the condition
to trigger an event.

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

Wa t l o w S e r i e s 9 6

P a r a m e t e r s

6 . 1 1

Setup Page / Output 2 Menu

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.

****

Output 1 and Output 2 menu prompts cannot have range selections set to identical control modes, e.g. Heat/Heat

or Cool/Cool if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .