Setup page / output 2 menu – Watlow Series 96 User Manual

Page 42

Advertising
background image

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.

Active if output 2 is present, but

is not a process type (not 96 _
_-_ A _ _-_ _ _ __ or 96 _ _-_ F_
_-_ _ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

725 r/w

[`yes] (1)

[``no] no (0)
[`yes] yes (1)

[Anu2] Alarm

Annunciation 2

Select alarm 2
annunciation option.

Active if output 2 is present, but

is not a process type (not 96 _
_-_ A _ _-_ _ _ __ or 96 _ _-_ F_
_-_ _ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

724 r/w

[AL`0] (0)

[Al`O] alarm condition

de-energizes output
(fail-safe operation)
(0)

[Al`C] alarm condition

energizes output (1)

[Lgc2] Alarm Logic 2

Select alarm 2 out-
put condition in the
alarm state.

Active if output 2 is present, but

is not a process type (not 96 _
_-_ A _ _-_ _ _ __ or 96 _ _-_ F_
_-_ _ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

723 r/w

[both] (0)

[both] both (0)
[``hi] high (1): high

side only

[``lo] low (2): low side

only

[Sid2] Alarm Active

Sides 2

Select which side or
sides the alarm set
points can be pro-
grammed for.

Active if output 2 is present, but

is not a process type (not 96 _
_-_ A _ _-_ _ _ __ or 96 _ _-_ F_
_-_ _ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

722 r/w

[``no] (0)

[``no] no action (0)
[`Yes] silence alarm

(1)

[SIL2] Silencing 2

Enable Silence 2.

Active if output 2 is present, but

is not a process type (not 96 _
_-_ A _ _-_ _ _ __ or 96 _ _-_ F_
_-_ _ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

721 r/w

[``no] (0)

[``no] no action (0)
[`Yes] latching en-

abled (1)

[LAT2] Latching 2

Enable Alarm 2
Latching.

Active if output 2 is present, but

is not process type (not 96 _ _-_
A _ _-_ _ _ __ or 96 _ _-_ F_ _-_
_ _ _), Output 2 (Output 2
Menu) is set to

[``AL] (Alarm)

and Setup Page Lock (Lockout
Menu) is not set to

[hide].

720 r/w

3°F, 2°C

1 to 9999

[ahy2] Alarm Hysteresis 2

Sets the switching
hysteresis for the
alarm output. This
defines a band on
the inside of the
alarm set point.
When the process
temperature is in
this band, the alarm
state will not
change.

6 . 1 2

P a r a m e t e r s

Wa t l o w S e r i e s 9 6

Setup Page / Output 2 Menu

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write