Operations page / pid 2 menu – Watlow Series 96 User Manual

Page 35

Advertising
background image

Active if Propband 2 (PID 2

Menu) is not set to

[```0],

Burst 2 (PID 2 Menu) is set to
[``no], output 2 is not a pro-
cess (not 96 _ _ - _ F _ _-_ _ _ _)
and Operations Page Lock
(Lockout Menu) is not set to
[hide].

516 r/w

Relay: 10.0

(100)

Solid-state:

1.0 (10)

Relay: 5.0 to 60.0 (50 to

600)

Solid-state: 0.1 to 60.0

(1 to 600)

[Ct`2] Cycle Time 2

Set the cycle time in
seconds for output 2.

Active if Propband 2 (PID 2

Menu) is not set to

[```0], and

Operations Page Lock (Lockout
Menu) is not set to

[hide], and

if Output 2 is equipped for a
solid-state relay (96A _-K _ _ _-
_ _ _ _) or switched dc (96A _-C
_ _ _-_ _ _ _) or voltage power
supply option (96A _-_ _ _ _-_ _
_ _.)

519 r/w

[``no] (0)

[``no] no (0)
[`Yes] yes (1)

[brs2] Burst 2

Select burst fire
mode for output 2.

Active if Propband 2 (PID 2

Menu) is not set to

[```0],

Units Type (Global Menu) is set
to

[``US] and Operations Page

Lock (Lockout Menu) is not set
to

[hide].

514 r/w

0.00 (0)

0.00 to 9.99 minutes

(0 to 999)

[rA`2] Rate 2

Set the rate time in
minutes for output
2.

Active if Propband 2 (PID 2

Menu) is not set to

[```0],

Units Type (Global Menu) is set
to

[``S1] and Operations Page

Lock (Lockout Menu) is not set
to

[hide].

513 r/w

0.00 (0)

0.00 to 9.99 minutes

(0 to 999)

[dE`2] Derivative 2

Set the derivative
time in minutes for
output 2.

Active if Propband 2 (PID 2

Menu) is not set to

[```0],

Units Type (Global Menu) is set
to

[``US] and Operations Page

Lock (Lockout Menu) is not set
to

[hide].

512 r/w

0.00 (0)

0.00 to 99.99 repeats

per minute (0 to 999)

[rE`2] Reset 2

Set the reset time in
repeats/minutes for
output 2.

Active if Propband 2 (PID 2

Menu) is not set to

[```0],

Units Type (Global Menu) is set
to

[``S1] and Operations Page

Lock (Lockout Menu) is not set
to

[hide].

511 r/w

0.00 (0)

0.00 to 99.99 minutes

per repeat (0 to 9999)

[It`2] Integral 2

Set the integral time
in minutes for out-
put 2.

Active if one output is set to heat

and the other to cool and Oper-
ations Page Lock (Lockout
Menu) is not set to

[hide] and

Heat-Cool Mode.

510 r/w

25°F, 14°C

0° to 9999°
If

[Pb`2] is set to 0 op-

erates in on/off mode.

[Pb`2] Propband 2

Set the proportional
band for output 2.

[PiD2]

PID 2 Menu

[Oper] Operations Page

Wa t l o w S e r i e s 9 6

P a r a m e t e r s

6 . 5

Operations Page / PID 2 Menu

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear

read/write

NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.