Setup page / global menu – Watlow Series 96 User Manual

Page 46

Advertising
background image

*These parameters are added if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .
**These parameters are removed if the ramping software option has been ordered (96 _ _ - _ _ _ _ - AA _ _ ) .
NOTE: For more information about how parameter settings affect the controller’s operation, see Chapter Five, Features.

Active if Failure Mode (Global

Menu) is set to

[MAn] (manu-

al) and Setup Page Lock (Lock-
out Menu) is not set to

[hide].

903 r/w

0.0 (0)

heat: 0.0 to 100.0

(0 to 1000)

cool: -100.0 to 0.0

(-1000 to 0)

heat/cool: -100.0 to

100.0 (-1000 to 1000)

[MAn] Manual Default

Power**

Select output power
for manual mode.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

902 r/w

[bPLS] (0)

[bPLS] bumpless (0)
[Man] manual (1)
[`OFF] off (2)

[FAIL] Failure Mode**

Select failure mode
after errors.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

607 r/w

[nLat] (1)

[`Lat] latching (0)
[nLat] no latching (1)

[`Err] Input Error Latch-

ing

Select input error
latching mode.

Active if Sensor Type 1 (Input 1

Menu) is set to RTD or thermo-
couple and Setup Page Lock
(Lockout Menu) is not set to
[hide].

901 r/w

[``°F] (0)

[``°F] °Fahrenheit (0)
[``°C] °Celsius (1)

[`C-F] °C or °F

Select the tempera-
ture scale for the
input. Converts all
temperature param-
eters.

Active if Setup Page Lock (Lock-

out Menu) is not set to

[hide].

900 r/w

[``Us] (1)

[``Us] propbands in

degrees, reset and
rate (1)

[``sI] propbands in

degrees, integral and
derivative (2)

[Unit] Units Type

Select US or SI units
of measurement.

[glbl]

Global Menu

[`set] Setup Page

****

Output 4 parameters

cannot be changed with the
Modbus interface.

Active if output 4 is equipped for

communications (96 _ _-_ _ _ R-
_ _ _ _ or 96 _ _-_ _ _ U-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to

[hide].

none****

1

1 to 247

[Addr] Address

Set communications
address.

Active if output 4 is equipped for

communications (96 _ _-_ _ _ R-
_ _ _ _ or 96 _ _-_ _ _ U-_ _ _ _)
and Setup Page Lock (Lockout
Menu) is not set to

[hide].

none****

[9600]

[1200] 1200
[2400] 2400
[4800] 4800
[9600] 9600
[1(20] 19.2K

[bAUd] Baud Rate

Set communications
baud rate.

Active if output 4 is equipped for

retransmit (96 _ _-_ _ _ M-_ _ _
_),

[Aout] (Analog Output 4) is

not set to

[`OFF] and Setup

Page Lock (Lockout Menu) is
not set to

[hide].

none****

0

-1999 to 9999

[ACAL] Analog Output

Offset

Set analog output
offset.

6 . 1 6

P a r a m e t e r s

Wa t l o w S e r i e s 9 6

Setup Page / Global Menu

Display

Parameter

Range

Default

Modbus

Conditions for

(Modbus Value)

Register

Parameters to Appear