<3. Parameter Setting>

3-14

IM 01C25R02-01E

• Procedure to call up the display using DD

(HART 5/HART 7) and DTM (HART 7)

PV related

parameter

[Root Menu] → Process variables →

Output vars → PV →

→ PV is

Current PV value

→ Change PV

Assgn

Select the variable assigned to PV

(Flow, Pres, SP, ET)

SV related

parameter

[Root Menu] → Process variables →

Output vars → SV →

→ SV is

Current SV value

→ Change SV

Assgn

Select the variable assigned to SV

(Flow, Pres, SP, ET, Total Flow)

TV related

parameter

[Root Menu] → Process variables →

Output vars → TV →

→ TV is

Current TV value

→ Change TV

Assgn

Select the variable assigned to TV

(Flow, Pres, SP, ET, Total Flow)

4V/QV related

parameter

[Root Menu] → Process variables →

Output vars → 4V/QV →

→ 4V is / QV is Current 4V/QV value
→ Change

4V Assgn

/Change QV

Assgn

Select the variable assigned to 4V/QV

(Flow, Pres, SP, ET, Total Flow)

• Procedure to call up the display using DTM

(HART 5)

PV related item Configuration → Output Variables →
→ PV is

Current PV value

→ Change PV

Assgn

Select the variable assigned to PV

(Flow, Pres, SP, ET)

It is similar about SV, TV and 4V.

The process variables that can be assigned are Flow,

Pres, SP, ET, and Total Flow.

3.2.3 Measuring Range

This section shows how to confirm and change

the parameters for measuring range of flow rate,

differential pressure, static pressure, external

temperature, and total flow, and also unit and

damping time constant.
These parameters are set at the factory before

shipment if specified at the time of order.
Follow the procedure below to change them.
About the differential pressure, static pressure and

external temperature, settable range are shown

on the parameters of LSL (Lower settable limit),

USL (Upper settable limit) and Min span (Minimum

span). Set the data within the range.

• Procedure to call up the display

Call up and setting of flow related parameters
DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → Flow Setup →

DTM (HART 5) Configuration → Flow →
→ Flow LRV

Lower range value for flow

→ Flow URV

Upper range value for flow

→ Flow Unit

Unit for flow

→ Flow Damp

Damping time constant for flow

Call up and setting of differential pressure related

parameters
DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → DP Setup (or Pres

Setup) →

DTM (HART 5) Configuration → Pressure Sensor →
→ Pres LRV

Lower range value for differential

pressure

→ Pres URV

Upper range value for differential

pressure

→ Pres Unit

Unit for differential pressure

→ Pres Damp

Damping time constant for differential

pressure

Call up and setting of static pressure related

parameters
DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → SP Setup →

DTM (HART 5) Configuration → Static Pressure

Sensor →

→ SP LRV

Lower range value for static pressure

→ SP URV

Upper range value for static pressure

→ SP Unit

Unit for static pressure

→ SP Damp

Damping time constant for static

pressure

Call up and setting of external temperature related

parameters
DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → ET Setup →

DTM (HART 5) Configuration → External

Temperature Sensor →

→ ET LRV

Lower range value for external

temperature

→ ET URV

Upper range value for external

temperature

→ ET Unit

Unit for external temperature

→ ET Damp

Damping time constant for external

temperature

Call up and setting of total flow related parameters
DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Signal condition → Total Flow →

DTM (HART 5) Configuration → Total Flow →
→ Total Flow

Unit

Unit for total flow