<4. Diagnostics>

4-3

IM 01C25R02-01E

NOTE

Time Stamp is reset when powering on.

(5) Configuration Change Counter

The Configuration Change Counter is

incremented once for every user action

that changes the device’s configuration or

calibration. This value is never reset or written

and maintained even if power is removed from

the device.

• Procedure to call up the display using DD

(HART 7) and DTM (HART 7)

DD (HART 7)

DTM (HART 7)

[Root Menu] → Diag/Service →

Status →

→ Cfg chng

count

The configuration change times

are counted. The counted value

cannot be reset.

(6) Reset Configuration Changed Flag

Configuration Changed Flag can be reset by

this method.

NOTE

Refer to Configuration Changed (0x40) in the

Table 4.7.

• Procedure to call up the display using DD

(HART 7) and DTM (HART 7)

DD (HART 7)

DTM (HART 7)

[Root Menu] → Diag/Service →

Status → Reset Cfg Chng flag

4.2 Advanced Diagnostics

4.2.1 Multi-sensing Process Monitoring

Multi-sensing process monitoring function (option

code: /DG6) provides the advanced diagnostics

to detect the abnormal conditions in process

environment such as an impulse line etc. by using

the EJX multisensing technology and its unique

algorithm. There are following two functions.

Impulse Line Blockage Detection (ILBD)

The fluctuation change of differential pressure and

static pressure is monitored by a silicone resonant

sensor and detects a potential blockage condition.

The differential pressure transmitter gives also a

result of which pressure-side was plugged.

Heat Trace Monitoring

The two temperature sensors built in the EJX

multivariable transmitter calculate the flange

temperature, the change of which enables to

detect the heat trace breakage or the abnormal

temperature due to the failure.

4.2.2 Impulse Line Blockage Detection

(ILBD)

ILBD is carried out by using statistical analysis

based on the measured values of process

fluctuations that exist in a fluid. An alarm on the EJX

multivariable transmitter LCD display or an analog

alert is generated if blockage reaches a certain

level. EJX multivariable transmitter provides the

following results as blockage detection.
(1) A Blocking and B Blocking

These are blockage detections based on

the fluctuation value change of differential

pressure/pressure. With a differential pressure

transmitter, each result indicates that both or

single side is plugged.

(2) L Side Blocking

It is a low-pressure side blockage detection

based on the change of

BlkF or low-pressure-

side fluctuation value.

(3) H Side Blocking

It is a high-pressure side blockage detection

based on the change of

BlkF or high-pressure-

side fluctuation value.

*:

BlkF indicates blockage degree characterized

by a comparison of the high- and low-pressure-

side fluctuation values. For the details, refer to

Figure 4.2.2.