<4. Diagnostics>

4-26

IM 01C25R02-01E

Integral

indicator

HART configuration

tool display

Cause

4-20mA Output

operation during error

Countermeasure

Status

group

*

1

Diagnostic

List

group *

2

AL.89

B BLK

B Blocking *

1

, *

2

B Blocking (both-side

blockage) is detected.

It depends on the Diag Out

Option setting.

Off: Continue to operate and

output.

Burnout: Outputs AO upper

limit or AO lower limit.

Fall back: Outputs Diag Out

Fixed Val.

Check process

condition.

10

D

ia

g

St

at

us

AL.89

H BLK

H Side Blocking *

1

High Side Blocking *

2

High-pressure-side

blockage is detected.

AL.89

L BLK

L Side Blocking *

1

Low Side Blocking *

2

Low-pressure-side

blockage is detected.

AL.89

H LRG

Large Fluct H *

1

Large Fluctuation of

High Side *

2

Pressure fluctuation

amplitude of high-

pressure side is large.

AL.89

L LRG

Large Fluct L *

1

Large Fluctuation of

Low Side *

2

Pressure fluctuation

amplitude of low-

pressure side is large.

AL.89

A BLK

A Blocking *

1

, *

2

A Blocking (single-side

blockage) is detected.

AL. 90

SIM

Flow Simulation

mode *

3

Simulation mode *

4

Under Simulation Mode

for flow.

Simulate input output.

Check Simulation

Mode.

5

Tr

an

sd

uc

er

St

at

us

AL. 91 *

3

F. SIM

F Simulate Mode

Under Simulation Mode

for device variables.

Output the setting value of

Simulate-Value

Check Simulation

Mode

11

AL. 91 *

3

P. SIM

P Simulate Mode

AL.91 *

3

SP. SIM

SP Simulate Mode

AL. 91 *

3

ET. SIM

ET Simulate Mode

AL. 91 *

3

TF. SIM

TF Simulate Mode

AL. 91 *

3

PCT. SIM

% Simulate Mode

AL. 91 *

3

AO. SIM

AO Simulate Mode

*1: DD (HART 5/HART 7), DTM (HART 7)

*2: DTM (HART 5)

*3: Available only for HART 7

*4: HART 5