3.3.16.2 In the case of using HART 7

“Multidropping” transmitters refer to the connection

of several transmitters to a single communication

transmission line. Up to 63 transmitters can be

connected when set in the multidrop mode. To

activate multidrop communication, the transmitter

address must be changed to a number from 1 to

63. This change deactivates the 4 to 20 mA analog

output, sending it to 4 mA. The alarm current is also

disabled.

Setting of Multidrop Mode

(1) Polling address

• Procedure to call up the display

DD (HART 7)

DTM (HART 7)

[Root Menu] → Detailed setup

→Output condition →HART

output →

→ Poll addr

Enter the number from 1 to 63

(2) Enabling the Multidrop Mode
About the procedure to call up the

Polling

display, please refer to the User’s Manual of each

configuration tool.
When

Loop current mode is set to “Enabled”, an

analog signal output is available for one device in a

loop.

• Procedure to call up the display

DD (HART 7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Output condition →Analog output →

Loop current mode →

Enabled

Loop current mode is enabled.

Disabled

Loop current mode is disabled.

NOTE

When the same polling address is set for

two or more transmitters in multidrop mode,

communication with these transmitters is

disabled.

(3) Communication when set in multidrop

mode.

• The HART configuration tool searches for a

transmitter that is set in multidrop mode when

it is turned on. When the HART configuration

tool is connected to the transmitter, the polling

address and the tag will be displayed.

• Select the desired transmitter. After that, normal

communication to the selected transmitter is

possible. However, the communication speed

will be slow.

To release multidrop mode, call up the

Poll addr

display and set the address to “0”.

3.3.17 Switching HART Protocol Revision

When the output signal code is “-J”, HART protocol

revision of EJX multivariable transmitter can be

selectable from 5 or 7.

The HART protocol revision is set and shipped as

specified in the order.

To change the HART protocol revision after

shipment, follow the procedure shown below.

IMPORTANT

When changing the protocol revision, confirm the

items below.

• Protocol revision supported by HART

configuration tool must be the same or

higher than new protocol revision of the EJX

multivariable transmitter. (Refer to Table 2.1)

• Confirm that the DD or DTM which is suitable

to new protocol revision of EJX multivariable

transmitter is installed in the configuration

tool. (Refer to Section 2.3 or 2.4)

1) Call up the parameter for protocol revision

change

• Procedure to call up the

Chg universal rev

display.

DD (HART 5/7)

DTM (HART 7)

[Root Menu] → Detailed setup →

Device information → Field device

info → Revision #’s → Chg universal

rev

DTM (HART 5) Configuration → HART → Chg

universal rev

2) Activate the “Chg universal rev” method

IMPORTANT

The message is displayed to separate the

transmitter from the automatic control loop.

Confirm that the transmitter is separated.

3) Input the new revision number

An input column for new protocol revision number is

displayed.

Input the new HART protocol revision number of “5”

for HART 5 or “7” for HART 7.