<3. Parameter Setting>

3-32

IM 01C25R02-01E

3.3.15 Burst Mode

3.3.15.1 In the case of using HART 5

When the

Burst mode is enabled, the transmitter

continuously sends the stored data. The data is

sent approximately three times per second as a

digital signal when the transmitter is set in burst

mode. When data is being sent in burst mode,

other operations can be performed with the HART

configuration tool.

(1) Selection of the transmission data.
Call up the

Burst option parameter and select the

data which is transferred.

• Procedure to call up the display

DD (HART 5)

[Root Menu] → Detailed setup →

Output condition

→ HART output → Burst option →

DTM (HART 5)

Configuration → HART → Burst

option →

Display Item

Contents

PV

Process variable assigned to PV

(Either of differential pressure, static

pressure, external temperature, and

flow rate)

%range/current Output in % and mA
Process vars/

crnt

Output in mA and process variables

assigned to PV, SV, TV, and 4V.

(Output in mA and four variables

from differential pressure, static

pressure, external temperature, flow

rate, and total flow.)

Xmtr Variables

Selectable up to four variables from

differential pressure, static pressure,

external temperature, flow rate, and

total flow.

According to the procedure indicated

in Burst Xmtr Vars, set the selected

variables to four Slot.

(For the Slot that is not used, set the

same value as others.)

(2) Shift to the Burst mode.
To enable the Burst mode, select “On” at the

Burst

mode parameter.

To release the

Burst mode, call up the Burst

mode display and set it to “Off”.

This parameter is set to “Off” when the instrument is

shipped.

• Procedure to call up the display

DD (HART 5)

[Root Menu] → Detailed setup →

Output condition → HART output →

Burst mode

DTM (HART 5)

Configuration → HART → Burst

mode

Display Item

Contents

Off

Stop the burst mode

On

Start the burst mode

3.3.15.2 In the case of using HART 7

When the

Burst mode is enabled, the transmitter

continuously sends up to three data listed in Table

3.8.

Refer to the subsection 3.3.15.2.1 Burst Message

for details.

When the

Burst mode is set to “Wired HART

Enabled”, transmitter continuously sends alarm

signal also.

Refer to subsection 3.3.15.2.2 Event Notification for

detail.

When changing the setting of

Burst mode, set “Off”

to the

Burst mode.

Default setting is “Off”.

3.3.15.2.1 Burst Message and Burst Mode

(1) Burst message
EJX multivariable transmitter can transmit three

burst messages at the maximum.

The parameters for

Burst Message are as follows.

• Burst Command

• Update Period and Max Update Period

• Burst Msg Trigger Mode