Parameter Setting Operations
3-5
IM 77C01E01-01E
1
2
3
4
5
A
I
3.3
Setting the Integrated Low-cut Power
Parameter Setting Types and Ranges
Parameter Symbol
Parameter Name
Setting
Type
Setting Range (Details)
Initial Value
(Factory-set
Value)
Integrated low-cut power
Fixed-point
numeric
value
0.05 to 20.00 (%)
0.05
Integrated low-cut power
This parameter is used to prevent active power (regenerative power), reactive power (LEAD/LAG) and
apparent power from being calculated as energy if they are smaller than the integrated low-cut power.
Set this parameter as a percent (%) of the rated power.