Parameter setting types and ranges – Yokogawa PR300 Power and Energy Meter User Manual

Page 34

Advertising
background image

Parameter Setting Operations

3-13

IM 77C01E01-01E

1

2

3

4

5

A

I

3.7

Setting Analog Output Conditions

To change the upper limit of scaling, set a new limit using
the parameter that follows.

Lower Limit of Scaling
screen

Lower limit of scaling setting
completed.

To return to the Analog Output Menu

screen, press .

Lower Limit of Scaling
Setting screen

Press once while
the setpoint is blinking.

The setpoint is confirmed and the PR300
returns to the Lower Limit of Scalling screen.

To return to the Measured Value

screen, hold down

.

If you do not operate any key for more
than 5 minutes on the Parameter
screen, the PR300 automatically
returns to the Measured Value screen.

11

NOTE

If the upper and lower limits of scaling do not satisfy the following conditional expression, the updated
upper or lower limit of scaling setpoint will not be incorporated but revert to the value before change.

Upper limit of scaling – Lower limit of scaling

м

50

Parameter Setting Types and Ranges

Analog output menu

Measurement item for
analog output

Lower limit of scaling

Upper limit of scaling

Selection

Fixed-point

numeric

value

Fixed-point

numeric

value

Active power

Reactive power

Apparent power

Voltage-1

Voltage-2

Voltage-3

Current-1

Current-2

Current-3

Power factor

Frequency

0.0 to 50.0 (%)

50.0 to 100.0 (%)

Active power

100.0

50.0

Menu to shift to the parameters of
analog output

Parameter Symbol

Parameter Name

Setting

Type

Setting Range (Details)

Initial Value

(Factory-set

Value)

Relationship between Scale Values and Measurement Inputs (Example)

4

20

-1000

0

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Lower

limit

Upper

limit

Scale values
to be set

100

0

1000

Output

mA

(W)

4

20

0

1000

Output

mA

(W)

50

100

When setting
output
proportional to
-1000 to 1000 W

When setting
output
proportional to
0 to 1000 W

Active power

4

20

-1000

(LEAD)

0

100

0

1000

(LAG)

Output

mA

(var)

Reactive power

4

20

0

0

100

1000

Output

mA

(VA)

Apparent power

4

20

0

1

0

100

600

Output

mA

(V)

Voltage

4

20

0

0

100

5

Output

mA

(A)

Current

4

20

45

0

100

65

Output

mA

(Hz)

Frequency

4

20

0.5

(LEAD)

0

100

0.5

(LAG)

Output

mA

Power factor

Scale values
to be set