Communication specifications, Demand alarm output specifications – Yokogawa PR300 Power and Energy Meter User Manual

Page 61

Advertising
background image

A-4

IM 77C01E01-01E

Appendix 1 Specifications of PR300

Demand Alarm Output Specifications (optional measuring function)

When the demand measurement value exceeds the set demand alarm point, an alarm is triggered.

Output signal

Open collector

Contact capacity

30 V DC, 200 mA

Set alarm range

1 to 1000 kW (during demand power measurement); 1 to 1000 A (during demand current measurement)

Alarm release function

Automatic release:When the measured value falls below the demand alarm point during alarm

output, the alarm is canceled.

Manual release:

Used to keep the alarm turned on or to cancel it by digital input or the
operation key, or via communication.

* The demand alarm mask time can be set for the PR300.

The demand alarm mask time is the time between the beginning of the demand period and the
set time, during which an alarm is not recognized.

Allowable range of set time: 1 minute to demand period

Communication Specifications

RS-485 communication

Via RS-485 communication, various measured values are read, and values are written to
various parameters using the command/response method.

Maximum communication distance: 1.2 km
Maximum number of connectable slave stations: 31

PC

Station number 01

Station number 02

Station number 31

(Example)

Protocol

PC link (without checksum), PC link (with checksum), Modbus/ASCII, and

Modbus/RTU

Transmission distance

Approximately 1.2 km maximum (with 24AWG twisted-pair cable(s))

Connection method

Multi-drop connection (a maximum of 32 units including a higher-level device)

Station number

01 to 99 (maximum number of units to be connected: 31 [number of units
that can be connected to a PC etc.]) (recommended value: 01 to 31)

Transmission method

Half-duplex communication

Synchronization

Start-stop synchronization

Baud rate

19200/9600/2400 bps

Xon/Xoff control

None

Data format

Data length

8 bits, 7 bits

Parity

None, even, odd

Stop bit

1 bit, 2 bits